Peukert Battery Runtime Calculator

Adjust a rated lead-acid capacity for a different constant discharge current using a supplied Peukert exponent.

Your inputs

Ah
h
A

Defaults are illustrative. Enter your battery or equipment data. Efficiency and usable capacity inputs are percentages.

Your result

Awaiting your inputs

Enter your values and press Calculate. Your result will appear here.

Explained formula · Sources listed below · No sign-up

The method

Formula and calculation steps

Runtime = rating hours × [Ah ÷ (rating hours × current A)] ^ exponent

The rated current is Ah divided by the rating period. The formula preserves rated runtime at that current, then adjusts runtime with the specified exponent.

Use a manufacturer-derived exponent and matching temperature and end voltage. This estimates time to the rating cutoff, without an added depth-of-discharge multiplier. It is unreliable at extreme currents.

Lead acid battery runtime and the Peukert exponent

A lead acid battery calculator must account for the discharge rate associated with the Ah rating. A 100 Ah capacity measured over 20 hours corresponds to a 5 A rated discharge current; it does not promise 100 A for one hour. Peukert runtime adjusts the rate effect while preserving the rating point.

Obtain the exponent from comparable discharge ratings or the manufacturer. This page assumes constant current, a consistent temperature and the same endpoint voltage as the rated test. It is not an electrochemical lead-acid reaction model or a Nernst-equation solver.

Worked example

A transparent starting point

100 Ah at the 20-hour rate, 10 A discharge and n = 1.2 gives 8.71 hours.

The values below are computed with the same formula as the calculator. They are examples, not manufacturer performance claims.

How one input changes the answer

Constant discharge current (A)Peukert runtime to rating cutoff
5 A20 hours
10 A8.705506 hours
15 A5.35161 hours

All other inputs use the illustrative defaults in the form.

Lead acid battery runtime and the Peukert exponent — calculated examples

Each row below is calculated from the stated case inputs. Inputs not changed in a row use the assumptions listed after the table.

CaseChanged inputsResult
5A, exponent 1Constant discharge current: 5 A; Peukert exponent: 1 20 hours
5A, exponent 1.2Constant discharge current: 5 A; Peukert exponent: 1.2 20 hours
10A, exponent 1Constant discharge current: 10 A; Peukert exponent: 1 10 hours
10A, exponent 1.2Constant discharge current: 10 A; Peukert exponent: 1.2 8.70551 hours
20A, exponent 1Constant discharge current: 20 A; Peukert exponent: 1 5 hours
20A, exponent 1.2Constant discharge current: 20 A; Peukert exponent: 1.2 3.78929 hours
40A, exponent 1Constant discharge current: 40 A; Peukert exponent: 1 2.5 hours
40A, exponent 1.2Constant discharge current: 40 A; Peukert exponent: 1.2 1.64938 hours

Unchanged inputs: Rated battery capacity = 100 Ah; Capacity rating period = 20 h; Constant discharge current = 10 A; Peukert exponent = 1.2 . Rows change only the listed inputs. Values are arithmetic examples, not manufacturer performance claims.

Common questions

Should I use 1.2 for every battery?

No. It is an illustrative input. Derive the exponent from two discharge ratings or use the manufacturer value.

How should I use the result?

Use a manufacturer-derived exponent and matching temperature and end voltage. This estimates time to the rating cutoff, without an added depth-of-discharge multiplier. It is unreliable at extreme currents.

What is the Peukert battery life calculation formula?

For capacity C rated over H hours and discharge current I, time is H × (C/(H×I))^n. The exponent n describes rate sensitivity. At the rated current C/H, the result is exactly H.

Can I use the lead acid formula for lithium-ion or LiFePO4?

Do not reuse a lead-acid exponent without supporting data. Rate dependence is chemistry- and product-specific. The basic energy runtime calculator is a better starting point when no validated exponent is available.

How is battery capacity at the 5-hour rate different from the 20-hour rate?

These are capacities measured at different discharge currents and may not be equal. Use ratings with matching cutoff and temperature when deriving the exponent.

Does an AGM battery use the same exponent as a flooded battery?

Not necessarily. AGM describes a construction, not one fixed Peukert exponent. Use the particular battery discharge data.

Sources and formula basis

Source addresses are shown as plain text. Algebraic rearrangements, example tables and user-selected loss factors are calculated on this site. A reference does not endorse every illustrative input.

  1. Victron BMV-700H manual §8 — battery capacity and Peukert exponenthttps://www.victronenergy.com/media/pg/BMV-700H/en/battery-capacity-and-peukert-exponent.html

Source pages checked: November 19, 2026. Verify current product data and locally adopted requirements before design or installation.