Adjust a rated lead-acid capacity for a different constant discharge current using a supplied Peukert exponent.
Your inputs
Your result
Awaiting your inputsEnter your values and press Calculate. Your result will appear here.
The method
Formula and calculation steps
Runtime = rating hours × [Ah ÷ (rating hours × current A)] ^ exponent
The rated current is Ah divided by the rating period. The formula preserves rated runtime at that current, then adjusts runtime with the specified exponent.
Use a manufacturer-derived exponent and matching temperature and end voltage. This estimates time to the rating cutoff, without an added depth-of-discharge multiplier. It is unreliable at extreme currents.
Lead acid battery runtime and the Peukert exponent
A lead acid battery calculator must account for the discharge rate associated with the Ah rating. A 100 Ah capacity measured over 20 hours corresponds to a 5 A rated discharge current; it does not promise 100 A for one hour. Peukert runtime adjusts the rate effect while preserving the rating point.
Obtain the exponent from comparable discharge ratings or the manufacturer. This page assumes constant current, a consistent temperature and the same endpoint voltage as the rated test. It is not an electrochemical lead-acid reaction model or a Nernst-equation solver.
Continue with: Battery Watt Hour Calculator · Battery Runtime Calculator
Worked example
A transparent starting point
100 Ah at the 20-hour rate, 10 A discharge and n = 1.2 gives 8.71 hours.
The values below are computed with the same formula as the calculator. They are examples, not manufacturer performance claims.
How one input changes the answer
| Constant discharge current (A) | Peukert runtime to rating cutoff |
|---|---|
| 5 A | 20 hours |
| 10 A | 8.705506 hours |
| 15 A | 5.35161 hours |
All other inputs use the illustrative defaults in the form.
Lead acid battery runtime and the Peukert exponent — calculated examples
Each row below is calculated from the stated case inputs. Inputs not changed in a row use the assumptions listed after the table.
| Case | Changed inputs | Result |
|---|---|---|
| 5A, exponent 1 | Constant discharge current: 5 A; Peukert exponent: 1 | 20 hours |
| 5A, exponent 1.2 | Constant discharge current: 5 A; Peukert exponent: 1.2 | 20 hours |
| 10A, exponent 1 | Constant discharge current: 10 A; Peukert exponent: 1 | 10 hours |
| 10A, exponent 1.2 | Constant discharge current: 10 A; Peukert exponent: 1.2 | 8.70551 hours |
| 20A, exponent 1 | Constant discharge current: 20 A; Peukert exponent: 1 | 5 hours |
| 20A, exponent 1.2 | Constant discharge current: 20 A; Peukert exponent: 1.2 | 3.78929 hours |
| 40A, exponent 1 | Constant discharge current: 40 A; Peukert exponent: 1 | 2.5 hours |
| 40A, exponent 1.2 | Constant discharge current: 40 A; Peukert exponent: 1.2 | 1.64938 hours |
Unchanged inputs: Rated battery capacity = 100 Ah; Capacity rating period = 20 h; Constant discharge current = 10 A; Peukert exponent = 1.2 . Rows change only the listed inputs. Values are arithmetic examples, not manufacturer performance claims.
Common questions
Should I use 1.2 for every battery?
No. It is an illustrative input. Derive the exponent from two discharge ratings or use the manufacturer value.
How should I use the result?
Use a manufacturer-derived exponent and matching temperature and end voltage. This estimates time to the rating cutoff, without an added depth-of-discharge multiplier. It is unreliable at extreme currents.
What is the Peukert battery life calculation formula?
For capacity C rated over H hours and discharge current I, time is H × (C/(H×I))^n. The exponent n describes rate sensitivity. At the rated current C/H, the result is exactly H.
Can I use the lead acid formula for lithium-ion or LiFePO4?
Do not reuse a lead-acid exponent without supporting data. Rate dependence is chemistry- and product-specific. The basic energy runtime calculator is a better starting point when no validated exponent is available.
How is battery capacity at the 5-hour rate different from the 20-hour rate?
These are capacities measured at different discharge currents and may not be equal. Use ratings with matching cutoff and temperature when deriving the exponent.
Does an AGM battery use the same exponent as a flooded battery?
Not necessarily. AGM describes a construction, not one fixed Peukert exponent. Use the particular battery discharge data.
Related calculators
Sources and formula basis
Source addresses are shown as plain text. Algebraic rearrangements, example tables and user-selected loss factors are calculated on this site. A reference does not endorse every illustrative input.
- Victron BMV-700H manual §8 — battery capacity and Peukert exponenthttps://www.victronenergy.com/media/pg/BMV-700H/en/battery-capacity-and-peukert-exponent.html