Battery Calculatorby Voltage Drop Calculator

Battery calculators / Packs & electrical

Understand your battery. Plan your power.

Battery Cable Voltage Drop Calculator

Calculate voltage drop and resistive loss using the cable manufacturer resistance per meter.

Your inputs

V
A
m
Ω/m

Defaults are illustrative. Enter your battery or equipment data. Efficiency and usable capacity inputs are percentages.

Your result

Awaiting your inputs

Enter your values and press Calculate. Your result will appear here.

Explained formula · Sources listed below · No sign-up

The method

Formula and calculation steps

Loop R = 2 × one-way m × Ω/m; drop V = current × loop R

The circuit includes outgoing and return conductors of equal length and resistance. Supplying actual operating-temperature resistance avoids pretending that an unspecified wire table applies.

This checks voltage drop only, not ampacity, fuse size or installation compliance. Add connections and unequal return paths separately. A drop at or above source voltage is outside the assumed operating point.

DC battery cable sizing by voltage drop

A battery cable size calculator must distinguish acceptable voltage drop from conductor ampacity. This tool evaluates drop when manufacturer cable resistance is already known. Enter one-way distance; the formula includes both outgoing and return conductors of equal length.

For battery-to-inverter wire size, operating current can be high at low voltage. Determine DC current from inverter demand and losses, then use resistance appropriate to the conductor operating temperature. Cable terminals, isolators, shunts and fuse holders add resistance not automatically included in the entered cable value.

Worked example

A transparent starting point

20 A through 3 m one way at 0.0033 Ω/m gives 0.396 V drop, 3.3% of 12 V and 7.92 W loss.

The values below are computed with the same formula as the calculator. They are examples, not manufacturer performance claims.

How one input changes the answer

One-way cable length (m)Cable voltage drop
1.5 m0.198 V
3 m0.396 V
4.5 m0.594 V

All other inputs use the illustrative defaults in the form.

DC battery cable sizing by voltage drop — calculated examples

Each row below is calculated from the stated case inputs. Inputs not changed in a row use the assumptions listed after the table.

CaseChanged inputsResult
1m one way, 10AOne-way cable length: 1 m; DC current: 10 A0.066 V
1m one way, 20AOne-way cable length: 1 m; DC current: 20 A0.132 V
3m one way, 10AOne-way cable length: 3 m; DC current: 10 A0.198 V
3m one way, 20AOne-way cable length: 3 m; DC current: 20 A0.396 V
5m one way, 10AOne-way cable length: 5 m; DC current: 10 A0.33 V
5m one way, 20AOne-way cable length: 5 m; DC current: 20 A0.66 V
10m one way, 10AOne-way cable length: 10 m; DC current: 10 A0.66 V
10m one way, 20AOne-way cable length: 10 m; DC current: 20 A1.32 V

Unchanged inputs: Nominal battery voltage = 12 V; DC current = 20 A; One-way cable length = 3 m; Cable resistance at operating temperature = 0.0033 Ω/m. Rows change only the listed inputs. Values are arithmetic examples, not manufacturer performance claims.

Common questions

Does this select a safe fuse?

No. Fuse current and interrupt rating depend on conductor ampacity, fault current, equipment and installation rules.

How should I use the result?

This checks voltage drop only, not ampacity, fuse size or installation compliance. Add connections and unequal return paths separately. A drop at or above source voltage is outside the assumed operating point.

How do I calculate a DC battery cable voltage drop?

Multiply one-way length by two, then by ohms per meter and amperes. Divide the resulting volts by source voltage for percent drop.

Does this choose an AWG battery wire size?

No. It checks the resistance you enter. Select candidate wire using manufacturer data and applicable ampacity rules, then compare the resulting drop.

Can the result choose a battery fuse size?

No. Fuse selection also depends on conductor protection, equipment requirements, voltage rating and interrupt capability. A low voltage drop does not establish protection adequacy.

What if my negative return has a different length?

Add the resistance of each actual conductor and connection. The simple form assumes equal outgoing and return conductor resistance; adjust the equivalent input or calculate the full loop separately.

Sources and formula basis

Source addresses are shown as plain text. Algebraic rearrangements, example tables and user-selected loss factors are calculated on this site. A reference does not endorse every illustrative input.

  1. Victron Wiring Unlimited §2 — electrical theory, cable resistance and voltage drophttps://www.victronenergy.com/media/pg/The_Wiring_Unlimited_book/en/theory.html
  2. Victron Wiring Unlimited §4 — DC wiring and protection considerationshttps://www.victronenergy.com/media/pg/The_Wiring_Unlimited_book/en/dc-wiring.html